UPS Inverter

Both sides of this UPS inverter are under a load of approximately 120A. There is, however, a 25° C temperature rise on the neutral side. The temperature measurements were performed on the cable insulation rather than the shiny connections, since the shinier surfaces mostly reflect cooler, background temperatures